- flight-wiki fully merged into airport-wiki/concepts/flight-operations/ - concepts/ restructured: tech-infrastructure/ (9 pages) + flight-operations/ (10 pages) - aodb.md (380 lines) split into aodb-core.md + aodb-vendors.md - SCHEMA.md updated: Domain covers '智算中心+航班運營' dual domains - new: airport-systems-landscape.md (flight ops system architecture) - index.md rewritten with visual directory tree - log.md updated
This commit is contained in:
@@ -0,0 +1,83 @@
|
||||
---
|
||||
title: 供配电与制冷
|
||||
created: 2026-04-08
|
||||
updated: 2026-04-09
|
||||
type: concept
|
||||
tags: [power, cooling, design]
|
||||
sources: [raw/articles/上海市-智算中心建设导则2025版-2025-01.md, raw/articles/头豹研究院-中国AIDC产业发展白皮书2025-2025-07.md]
|
||||
---
|
||||
|
||||
# 供配电与制冷
|
||||
|
||||
## 供配电系统
|
||||
|
||||
### 典型架构
|
||||
```
|
||||
市电 → ATS → UPS → PDU → 服务器
|
||||
↑ ↑
|
||||
柴油发电机 蓄电池
|
||||
```
|
||||
|
||||
### 关键指标
|
||||
- **IT 负载功率密度**:通常 4-10 kW/机柜(传统DC);智算中心单柜 **12-30kW**
|
||||
- **PUE 目标值**:1.3-1.5(传统机场DC);智算中心需达 **≤1.22**(上海导则先进值≤1.18)
|
||||
- **市电引入**:双路 10kV 或 35kV
|
||||
- **UPS 容量**:N+1 或 2N 冗余
|
||||
- **上海导则选址供电要求**:市电平均每月停电次数 ≤ 1次;平均每次故障时间 ≤ 0.5小时;宜引入一类市电
|
||||
|
||||
### 柴油发电机
|
||||
- 常用功率:1000-3000 kVA
|
||||
- 启动时间:< 10 秒(自动启动)
|
||||
- 储油量:满足 8-24 小时连续运行
|
||||
|
||||
## 制冷系统
|
||||
|
||||
### 冷却方式
|
||||
|
||||
| 方式 | PUE范围 | 适用场景 |
|
||||
|------|---------|---------|
|
||||
| **液冷(相变浸没式)** | **1.00** | >30kW/机柜,超大规模智算 |
|
||||
| **液冷(冷板式)** | **~1.10** | 高密度智算中心(主流方案) |
|
||||
| 自然冷(间接蒸发冷) | 1.10-1.20 | 北方气候区 |
|
||||
| 冷冻水系统 | 1.30+ | 传统数据中心 |
|
||||
| 风冷 | 1.40+ | 面临淘汰 |
|
||||
|
||||
> 数据来源:头豹研究院《中国AIDC产业发展白皮书2025》——液冷已成PUE<1.10核心路径,传统风冷进入结构性瓶颈
|
||||
|
||||
### 上海智算中心2025 PUE要求(全国最严)
|
||||
|
||||
| 指标 | 新建准入值 | 运营先进值 | 长三角集群 |
|
||||
|------|------------|------------|------------|
|
||||
| **基准PUE** | ≤ 1.25 | — | — |
|
||||
| **综合PUE** | ≤ 1.22 | ≤ 1.18 | ≤ 1.20 |
|
||||
| **WUE** | ≤ 2.2 L/kWh | ≤ 2.0 L/kWh | — |
|
||||
| **CUE** | ≤ 1.2 gCO2/kWh | ≤ 1.0 gCO2/kWh | — |
|
||||
|
||||
> 来源:上海市《智算中心建设导则(2025年版)》
|
||||
|
||||
### 液冷技术类型
|
||||
|
||||
| 类型 | PUE | 单柜散热能力 | 建设成本 | 适用 |
|
||||
|------|-----|------------|---------|------|
|
||||
| **冷板式液冷** | ~1.10 | ~120kW/柜 | 中 | 主流,新建智算中心首选 |
|
||||
| **浸没式液冷(相变)** | **1.00** | >200kW/柜 | 高 | 超大规模(GB200 NVL72等) |
|
||||
| **风液混合** | 1.10-1.15 | 60-150kW/柜 | 中低 | 快速部署/改造场景 |
|
||||
|
||||
国产液冷供应商参考:
|
||||
- **英维克**:冷板式液冷,单机柜功率密度24kW,散热效率提升40%
|
||||
- **中科曙光**:浸没式液冷,PUE低至1.04,年减碳量超万吨
|
||||
|
||||
### 机场数据中心推荐
|
||||
|
||||
- 航站楼主数据中心:液冷(冷板式)成为新建首选,液冷渗透率已达64%(工业智算场景)
|
||||
- 边缘小机房:风冷精密空调(过渡方案,逐步被边缘液冷替代)
|
||||
- **强制要求**:新建智算中心**宜采用液冷技术**(上海导则)
|
||||
|
||||
## PUE 优化建议
|
||||
|
||||
- 冷热通道封闭
|
||||
- 自然冷却(冬季)
|
||||
- 精确制冷(行级空调)
|
||||
- 高效 UPS(模块化效率 ≥ 96%)
|
||||
|
||||
> 相关:[[tier-iii-design]] | [[tier-iv-design]] | [[glossary]]
|
||||